Overview
The Core Real-Time Data is a Certified Product Point Template for Solar Farms defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all solar farms. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio.
This point template provides a reliable baseline of data at the site level aggregated from both the PV Inverter and Meters modeled in Bazefield. The purpose is to:
Ensure consistent naming and normalization of critical telemetry available on all makes and models of inverters on different solar farms
Support cross-site and cross-technology data normalization
Template Definition
The Core Real-Time Data template contains solar farm level calculations summarizing Inverter and Meter SCADA values. Details on the Point Names, Descriptions, and Types are below.
Required for Bazefield Core Dashboard functionality
Optional for common additional data streams/sources
Name | Description | Type | Interval | Units | |
---|---|---|---|---|---|
ActivePowerINV | Sum of inverter Active Power in MW | Interval Calc | 300 s | MW | |
ActivePowerMeter | Sum of check meter power in MW | Online Calc | Real-Time | MW | |
Current | Total current from check meter | Online Calc | Real-Time | A | |
Irradiance | Average irradiance from weather stations | Online Calc | Real-Time | w/m2 | |
PowerFactor | Average Power Factor from check meter | Online Calc | Real-Time | % | |
ReactivePowerINV | Sum of inverter Reactive Power in MVAR | Interval Calc | 300 | MVAR | |
ReactivePowerMeter | Sum of check meter Reactive Power in MVAR | Online Calc | Real-Time | MVAR | |
Voltage | Average voltage (HS bus) from check meter | Online Calc | Real-Time | kV |