Overview
The Core Real-Time Data is a Certified Product Point Template for Power Plant Controllers which defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all Power Plant Controllers. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio.
This point template provides a reliable baseline of real-time data expected from each Power Plant Controller modeled in Bazefield. The purpose is to:
Ensure consistent naming and normalization of critical telemetry available on all makes and models of Power Plant Controllers
Streamline configuration for SCADA or historian data ingestion
Support cross-site and cross-technology data normalization
Template Definition
The Core Real-Time Data point template includes telemetry definitions for standard power plant controller measurements. PPC data is optional, and it not required for Bazefield Core needs. Details on the Point Names, Descriptions, and Types are below.
Required for Bazefield Core Dashboard functionality
Optional for common additional data streams/sources
Name | Description | Type | Unit | |
|---|---|---|---|---|
ActivePower | Site active power from plant meter closest to POI. | SCADA (raw) | MW | |
ActivePowerSetpoint | Plant power setpoint. | SCADA (raw) | MW | |
AssetsAvailable | Number of assets available from OEM PPC | SCADA (raw) | ||
AssetsCommunicating | Number of assets communicating from OEM PPC | SCADA (raw) | ||
AssetsCurtailed | Number of assets in curtailed state from OEM PPC | SCADA (raw) | ||
AssetsHighResource | Number of assets in high resource (wind/irradiance) cutout from OEM PPC | SCADA (raw) | ||
AssetsLowResource | Number of assets in low resource (wind/irradiance) cutout from OEM PPC | SCADA (raw) | ||
AssetsOnline | Number of assets online/running, producing power, from OEM PPC | SCADA (raw) | ||
AssetsStop | Number of assets stopped from OEM PPC | SCADA (raw) | ||
CurrentA | Phase A current from OEM PPC | SCADA (raw) | A | |
CurrentB | Phase B current from OEM PPC | SCADA (raw) | A | |
CurrentC | Phase C current from OEM PPC | SCADA (raw) | A | |
CurtailmentFlag | Plant power is curtailed. | SCADA (raw) | ||
Frequency | Frequency from OEM PPC | SCADA (raw) | Hz | |
PossiblePower | Possible power (MW) from OEM PPC | SCADA (raw) | MW | |
PowerFactor | Power factor from OEM PPC | SCADA (raw) | ||
ReactivePower | Site reactive power from OEM PPC | SCADA (raw) | MVAR | |
Voltage | Site voltage from OEM PPC | SCADA (raw) | kV | |
WindDirection | Site wind direction from OEM PPC | SCADA (raw) | Deg | |
WindSpeed | Site wind speed from OEM PPC | SCADA (raw) | m/s |