Core Real-Time Data

Prev Next

Overview

The Core Real-Time Data is a Certified Product Point Template for Meter which defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all Meters. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio.

This point template provides a reliable baseline of real-time data expected from each Meter modeled in Bazefield. The purpose is to:

  • Ensure consistent naming and normalization of critical telemetry available on all makes and models of Meters

  • Streamline configuration for SCADA or historian data ingestion

  • Support cross-site and cross-technology data normalization

Template Definition

The Core Real-Time Data point template includes telemetry definitions for standard meter measurements. Meter data is useful at a site level, and is often compared to aggregations of generating asset data. Details on the Point Names, Descriptions, and Types are below.

Required for Bazefield Core Dashboard functionality

Optional for common additional data streams/sources

Name

Description

Type

Unit

ActivePower

Three phase active power total

SCADA (raw)

MW

ActivePowerA

Active power phase A

SCADA (raw)

MW

ActivePowerB

Active power phase B

SCADA (raw)

MW

ActivePowerC

Active power phase C

SCADA (raw)

MW

ApparentPower

Three phase apparent power total

SCADA (raw)

MVA

ApparentPowerA

Apparent power phase A

SCADA (raw)

MVA

ApparentPowerB

Apparent power phase B

SCADA (raw)

MVA

ApparentPowerC

Apparent power phase C

SCADA (raw)

MVA

CommunicationState

Communication state (Bazefield calculated) 1= bad comms

SCADA (raw)

Current

Total current of three phases

SCADA (raw)

A

CurrentA

Current phase A

SCADA (raw)

A

CurrentB

Current phase B

SCADA (raw)

A

CurrentC

Current phase C

SCADA (raw)

A

Frequency

Frequency

SCADA (raw)

Hz

PowerFactor

Power factor

SCADA (raw)

%

PowerFactorA

Power factor phase A

SCADA (raw)

%

PowerFactorB

Power factor phase B

SCADA (raw)

%

PowerFactorC

Power factor phase C

SCADA (raw)

%

ReactivePower

Three phase reactive power total

SCADA (raw)

MVAR

ReactivePowerA

Reactive power phase A

SCADA (raw)

MVAR

ReactivePowerB

Reactive power phase B

SCADA (raw)

MVAR

ReactivePowerC

Reactive power phase C

SCADA (raw)

MVAR

TotalEnergyConsumed

Lifetime energy consumed

SCADA (raw)

MWh

TotalEnergyProduced

Lifetime energy produced

SCADA (raw)

MWh

Voltage

Average three phase line to line voltage

SCADA (raw)

kV

VoltageAB

Voltage line to line phase AB

SCADA (raw)

kV

VoltageAN

Voltage line to neutral phase A

SCADA (raw)

kV

VoltageBC

Voltage line to line phase BC

SCADA (raw)

kV

VoltageBN

Voltage line to neutral phase B

SCADA (raw)

kV

VoltageCA

Voltage line to line phase CA

SCADA (raw)

kV

VoltageCN

Voltage line to neutral phase C

SCADA (raw)

kV