Overview

The Core Real-Time Data is a Certified Product Point Template for Power Conversion Systems that defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all power conversion systems. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio.

This point template provides a reliable baseline of real-time data expected from each Power Conversion System modeled in Bazefield. The purpose is to:

  • Ensure consistent naming and normalization of critical telemetry available on all makes and models of power conversion systems

  • Streamline configuration for SCADA or historian data ingestion

  • Support cross-site and cross-technology data normalization

The Core Real-Time Data template defines 29 standard data streams for Power Conversion Systems. A Bazefield Power Conversion System is appropriate for modelling traditional Battery Inverters, as well as single unit Battery Inverter/Container systems such as Tesla MegaPacks.

Template Definition

The Core Real-Time Data template contains standard data streams for Power Conversion System SCADA data. Details on the Point Names, Descriptions, and Types are below. The Core Real-Time Data template specifically holds all the critical “raw” data expected from all Power Conversion System SCADA systems.

Minimum Requirements: In most modern power conversion systems, there will be a significant number of points available beyond this list which are vendor or SCADA specific. This list represents the minimum, common list of critical data often available in ALL vendors and SCADA systems. Many of the points below are used directly in Bazefield core functionality, or core performance calculations.

Required for Bazefield Core Dashboard functionality

Optional for common additional data streams/sources

Point Definition Table

Name

Description

Type

Unit

ActivePower

AC ActivePower

Raw Data

kW

AmbientTemperature

Ambient Temperature

Raw Data

°C

ApparentPower

Apparent Power

Raw Data

kVA

CellTempAvg

Average temperature of cells in the PCS.  Otherwise, calculated by Scale Equation as an average of this PCS's battery containers (Dictated by the "Reference Container" object attributes).

Raw Data

°C

CellTempMax

Maximum cell temperature in the PCS.  Otherwise, calculated by Scale Equation as an average of this PCS's battery containers (Dictated by the "Reference Container" object attributes).

Raw Data

°C

CellTempMin

Minimum cell temperature in the PCS.  Otherwise, calculated by Scale Equation as an average of this PCS's battery containers (Dictated by the "Reference Container" object attributes).

Raw Data

°C

Current

Grid Current Total

Raw Data

A

CurrentA

Grid Current Phase A

Raw Data

A

CurrentB

Grid Current Phase B

Raw Data

A

CurrentC

Grid Current Phase C

Raw Data

A

DC-Current

DC Current drawn from battery container(s)

Raw Data

A

DC-Power

DC Power drawn from battery container(s)

Raw Data

kW

DC-Voltage

DC Voltage of battery container(s)

Raw Data

V

ErrorCode

Current ErrorCode reported by the PCS or battery inverter

Raw Data

Frequency

Grid Frequency

Raw Data

Hz

OperationState

Current raw OperationState of the PCS or battery inverter

Raw Data

PowerChargeLimit

AC Chargeable Power Limit

Raw Data

kW

PowerDischargeLimit

AC Dischargeable Power Limit

Raw Data

kW

PowerFactor

Power Factor

Raw Data

PF

ReactivePower

Reactive Power

Raw Data

kVAr

SetpointActivePower

Active Power Setpoint for the PCS

Raw Data

kW

SetpointReactivePower

Reactive Power Setpoint

Raw Data

kVAr

StateOfCharge

State of Charge (SOC). Retrieved from data source directly, if available. Otherwise, calculated by Scale Equation as an average of this PCS's battery containers (Dictated by the "Reference Container" object attributes).

Raw Data

%

TotalEnergyCharged

Cumulative energy charged from OEM SCADA counter

Raw Data

kWh

TotalEnergyDischarged

Cumulative energy discharged from OEM SCADA counter

Raw Data

kWh

Voltage

Grid Voltage (mean)

Raw Data

V

VoltageAB

Grid Voltage A-B

Raw Data

V

VoltageBC

Grid Voltage B-C

Raw Data

V

VoltageCA

Grid Voltage C-A

Raw Data

V