Overview
The Core Real-Time Data is a Certified Product Point Template for Power Conversion Systems that defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all power conversion systems. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio.
This point template provides a reliable baseline of real-time data expected from each Power Conversion System modeled in Bazefield. The purpose is to:
Ensure consistent naming and normalization of critical telemetry available on all makes and models of power conversion systems
Streamline configuration for SCADA or historian data ingestion
Support cross-site and cross-technology data normalization
The Core Real-Time Data template defines 29 standard data streams for Power Conversion Systems. A Bazefield Power Conversion System is appropriate for modelling traditional Battery Inverters, as well as single unit Battery Inverter/Container systems such as Tesla MegaPacks.
Template Definition
The Core Real-Time Data template contains standard data streams for Power Conversion System SCADA data. Details on the Point Names, Descriptions, and Types are below. The Core Real-Time Data template specifically holds all the critical “raw” data expected from all Power Conversion System SCADA systems.
Minimum Requirements: In most modern power conversion systems, there will be a significant number of points available beyond this list which are vendor or SCADA specific. This list represents the minimum, common list of critical data often available in ALL vendors and SCADA systems. Many of the points below are used directly in Bazefield core functionality, or core performance calculations.
Required for Bazefield Core Dashboard functionality
Optional for common additional data streams/sources
Point Definition Table
Name | Description | Type | Unit | |
|---|---|---|---|---|
ActivePower | AC ActivePower | Raw Data | kW | |
AmbientTemperature | Ambient Temperature | Raw Data | °C | |
ApparentPower | Apparent Power | Raw Data | kVA | |
CellTempAvg | Average temperature of cells in the PCS. Otherwise, calculated by Scale Equation as an average of this PCS's battery containers (Dictated by the "Reference Container" object attributes). | Raw Data | °C | |
CellTempMax | Maximum cell temperature in the PCS. Otherwise, calculated by Scale Equation as an average of this PCS's battery containers (Dictated by the "Reference Container" object attributes). | Raw Data | °C | |
CellTempMin | Minimum cell temperature in the PCS. Otherwise, calculated by Scale Equation as an average of this PCS's battery containers (Dictated by the "Reference Container" object attributes). | Raw Data | °C | |
Current | Grid Current Total | Raw Data | A | |
CurrentA | Grid Current Phase A | Raw Data | A | |
CurrentB | Grid Current Phase B | Raw Data | A | |
CurrentC | Grid Current Phase C | Raw Data | A | |
DC-Current | DC Current drawn from battery container(s) | Raw Data | A | |
DC-Power | DC Power drawn from battery container(s) | Raw Data | kW | |
DC-Voltage | DC Voltage of battery container(s) | Raw Data | V | |
ErrorCode | Current ErrorCode reported by the PCS or battery inverter | Raw Data | — | |
Frequency | Grid Frequency | Raw Data | Hz | |
OperationState | Current raw OperationState of the PCS or battery inverter | Raw Data | — | |
PowerChargeLimit | AC Chargeable Power Limit | Raw Data | kW | |
PowerDischargeLimit | AC Dischargeable Power Limit | Raw Data | kW | |
PowerFactor | Power Factor | Raw Data | PF | |
ReactivePower | Reactive Power | Raw Data | kVAr | |
SetpointActivePower | Active Power Setpoint for the PCS | Raw Data | kW | |
SetpointReactivePower | Reactive Power Setpoint | Raw Data | kVAr | |
StateOfCharge | State of Charge (SOC). Retrieved from data source directly, if available. Otherwise, calculated by Scale Equation as an average of this PCS's battery containers (Dictated by the "Reference Container" object attributes). | Raw Data | % | |
TotalEnergyCharged | Cumulative energy charged from OEM SCADA counter | Raw Data | kWh | |
TotalEnergyDischarged | Cumulative energy discharged from OEM SCADA counter | Raw Data | kWh | |
Voltage | Grid Voltage (mean) | Raw Data | V | |
VoltageAB | Grid Voltage A-B | Raw Data | V | |
VoltageBC | Grid Voltage B-C | Raw Data | V | |
VoltageCA | Grid Voltage C-A | Raw Data | V |