Overview
The Core Real-Time Data is a Certified Product Point Template for Battery Containers that defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all battery containers. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio.
This point template provides a reliable baseline of real-time data expected from each Battery Container modeled in Bazefield. The purpose is to:
- Ensure consistent naming and normalization of critical telemetry available on all makes and models of battery containers
- Streamline configuration for SCADA or historian data ingestion
- Support cross-site and cross-technology data normalization
The Core Real-Time Data template defines 24 standard data streams for Battery Containers. Battery Containers represent the physical battery enclosures that house one or more battery racks/strings connected to a Power Conversion System.
Template Definition
The Core Real-Time Data template contains standard data streams for Battery Container SCADA data. Details on the Point Names, Descriptions, and Types are below. The Core Real-Time Data template specifically holds all the critical “raw” data expected from all Battery Container SCADA systems.
Minimum Requirements: In most modern battery containers, there will be a significant number of points available beyond this list which are vendor or SCADA specific. This list represents the minimum, common list of critical data often available in ALL vendors and SCADA systems. Many of the points below are used directly in Bazefield core functionality, or core performance calculations.
Required for Bazefield Core Dashboard functionality
Optional for common additional data streams/sources
Point Definition Table
| Name | Description | Type | Unit | |
|---|---|---|---|---|
| CellTempAvg | Average temperature of cells in the container | Raw Data | °C | |
| CellTempMax | Maximum cell temperature in the container | Raw Data | °C | |
| CellTempMin | Minimum cell temperature in the container | Raw Data | °C | |
| CellVoltageAvg | Average voltage of cells in the container | Raw Data | V | |
| CellVoltageMax | Maximum cell voltage in the container | Raw Data | V | |
| CellVoltageMin | Minimum cell voltage in the container | Raw Data | V | |
| ChargeCurrentMax | Instantaneous maximum DC charge current. | Raw Data | A | |
| DC-Current | Total DC current flowing to/from battery container | Raw Data | A | |
| DC-Power | Total power flowing to/from battery container | Raw Data | kW | |
| DC-Voltage | Total DC Voltage on the container | Raw Data | V | |
| DischargeCurrentMax | Instantaneous maximum DC discharge current. | Raw Data | A | |
| PowerChargeLimit | DC Chargeable Power Limit | Raw Data | kW | |
| PowerDischargeLimit | DC Dischargeable Power Limit | Raw Data | kW | |
| RackCurrentAvg | Average string/rack current for all strings/racks in the container | Raw Data | A | |
| RackCurrentMax | Maximum current of any rack/string in the container | Raw Data | A | |
| RackCurrentMin | Minimum current of any rack/string in the container | Raw Data | A | |
| RackVoltageAvg | Average string/rack voltage for all strings/racks in the container | Raw Data | V | |
| RackVoltageMax | Maximum rack/string voltage for all racks/strings in the container | Raw Data | V | |
| RackVoltageMin | Minimum rack/string voltage for all racks/strings in the container | Raw Data | V | |
| StateOfCharge | Amount of charge in the container, expressed as a percentage | Raw Data | % | |
| StateOfChargeMaxLimit | Maximum State of Charge Limit | Raw Data | % | |
| StateOfChargeMinLimit | Minimum State of Charge Limit | Raw Data | % | |
| StateOfHealth | State of Health (SOH) | Raw Data | % | |
| TempInternal | Internal container ambient air temperature. Distinct from cell temperatures — used for thermal management and HVAC diagnostics. | Raw Data | °C |