Documentation Index

Fetch the complete documentation index at: https://docs.bazefield.com/llms.txt

Use this file to discover all available pages before exploring further.

Core Real-Time Calculations

Prev Next

Overview

The Core Real-Time Calculations is a Certified Product Point Template for Power Conversion Systems that defines required normalized real-time performance calculations that scale, or transform several of the points in the Core Real-Time Data. These points are required for the Bazefield installation to function properly across all core applications.

These calculations specifically translate OEM-specific signals into consistent indicators of operational state, availability, communication status, and event conditions. By abstracting vendor-specific complexities, the Core Real-Time Calculations enables unified fleet monitoring, reduces configuration overhead, and supports consistent reporting and alarm management across heterogeneous power conversion systems technologies.

The Core Real-Time Calculations template defines 24 calculations for Power Conversion Systems. These calculations derive operational state, charge/discharge status, communication health, and data quality indicators from raw real-time data.

Template Definition

The Core Real-Time Calculations is defined below. Calculations are one of the following types:

  • Scale Equations — Algebraic or logical manipulations of input data done on the Bazefield edge buffer

  • Online Expressions — Algebraic or logical manipulations of input data done on the central Bazefield data engines (typically on a storage node). Similar to scale equations in purpose, but done in the centralized architecture.

  • Interval Expressions — Algebraic, logical, or advanced manipulations of input data done within a pre-defined aggregation interval (e.g. 5 minutes, 10 minutes, 1 hour, etc). These are typically done centrally on a storage node.

Details on the Point Names, Descriptions, and Types are below.

Required for Bazefield Core Dashboard functionality

Optional for common additional data streams/sources

Calculation Definition Table

Name

Description

Type

Interval

Units

Available

Real time availability (1=available, 0=unavailable).

Calculation (Scale Eq)

Real-time

Charging

PCS is Charging. (Dictated by OEM Status or "Charging Threshold" object attribute.)

Calculation (Scale Eq)

Real-time

ChargingPower

Power drawn by PCS battery container(s) while it is charging. (Dictated by "Charging Threshold" object attribute.)

Calculation (Scale Eq)

Real-time

kW

CommunicationState

PCS communication state (0=connected, 1=No reply from server, 2=Session could not be created, 3=One of Baze core items failed, 4=Baze core items in flatline, 5=Baze core items in bad quality)

Calculation (Scale Eq)

Real-time

Discharging

PCS is Discharging. (Dictated by OEM Status or "Discharging Threshold" object attribute.)

Calculation (Scale Eq)

Real-time

DischargingPower

Power provided by PCS battery container(s) while it is discharging. (Dictated by "Discharging Threshold" object attribute.)

Calculation (Scale Eq)

Real-time

kW

EVENT-BadActivePower

Data quality flag if the Active Power measurement has not reported or is reporting bad/invalid data while charging or discharging. 0=good, 1=disconnected/null, 4=stale data, 5=bad quality

Calculation (Scale Eq)

Real-time

EVENT-BadStateOfCharge

Data quality flag if the State of Charge measurement has not reported or is reporting bad/invalid data. 0=good, 1=disconnected/null, 4=stale data, 5=bad quality

Calculation (Scale Eq)

Real-time

EVENT-Charged

Boolean indicating that the PCS has reached its maximum charge capacity limit. (Dictated by "Fully Charged Threshold" object attribute.)

Calculation (Scale Eq)

Real-time

EVENT-Charging

Boolean indicating that the PCS is charging for the last 5 minutes. Used to drive PCS events.

Calculation (Interval Exp.)

5 min

EVENT-Discharged

Boolean indicating that the PCS has reached its minimum charge capacity limit. (Dictated by "Fully Discharged Threshold" object attribute.)

Calculation (Scale Eq)

Real-time

EVENT-Discharging

Boolean indicating that the PCS is discharging for the last 5 minutes. Used to drive PCS events.

Calculation (Interval Exp.)

5 min

EVENT-Idle

Boolean indicating that the PCS is neither charging nor discharging for the last 5 minutes. Used to drive PCS events.

Calculation (Interval Exp.)

5 min

EVENT-NotChargingWithSetpoint

Boolean indicating that the PCS has a negative (-) setpoint, but is not charging power

Calculation (Scale Eq)

Real-time

EVENT-NotDischargingWithSetpoint

Boolean indicating that the PCS has a positive (+) setpoint, but is not discharging power

Calculation (Scale Eq)

Real-time

IEC-OperationState

PCS high-level Operation State. (1=Stop, 2=Standby, 3=Starting, 4=Run, 99=Unknown.) To be configured per OEM.

Raw Data

Real-time

Mode

PCS Mode usually dictated by the EMS. (E.G., Grid support, VAR support, frequency support, arbitrage, black start) To be configured per OEM.

Raw Data

Real-time

Reporting

Boolean describing if the PCS is communicating based off of CommunicationState tag, 0=bad comms, 1=good comms

Calculation (Scale Eq)

Real-time

Running

PCS is running (IEC-OperationState = 4)

Calculation (Scale Eq)

Real-time

Standby

PCS is in Standby (IEC-OperationState = 2)

Calculation (Scale Eq)

Real-time

Status

Single tag returning the current status of the PCS. (5 = Ancillary Services, 4 = Discharging, 3 = Charging, 2 = Standby, 1=Stopped, 99 = Unknown.) To be configured per OEM.

Raw Data

Real-time

Stopped

PCS is stopped (IEC-OperationState = 1)

Calculation (Scale Eq)

Real-time

Unavailable

Boolean describing if the PCS is unavailable (IEC-OperationState = 1) 1=unavailable, 0=available.

Calculation (Scale Eq)

Real-time

Unknown

Boolean describing if the PCS state is unknown (IEC-OperationState = 99) 1=unknown state, 0=known state.

Calculation (Scale Eq)

Real-time