The Core Real-Time Data template contains standard data streams at the AC level from Inverter sensors. Details on the Point Names, Descriptions, and Types are below.
Required for Bazefield Core Dashboard functionality
Optional for common additional data streams/sources
Name | Description | Type | |
---|---|---|---|
ActivePower | Active power measured from Inverter | SCADA | |
AmbientTemperature | Ambient temperature measured from Inverter | SCADA | |
Current | Real time current measured from Inverter | SCADA | |
CurrentA | Real time current in phase A, typically from OPC interface | SCADA | |
CurrentB | Real time current in phase B, typically from OPC interface | SCADA | |
CurrentC | Real time current in phase C, typically from OPC interface | SCADA | |
ErrorCode | Real time error code (single tag) for OEM vendor, typically from an OPC interface | SCADA | |
Frequency | Real time frequency in Hz measured from Inverter | SCADA | |
OperationState | Operating state for the Inverter, typically from an OPC interface | SCADA | |
PowerFactor | Real time power factor measured from Inverter | SCADA | |
ReactivePower | Reactive power measured from inverter | SCADA | |
TotalEnergyProduced | Energy produced from OEM SCADA counter | SCADA | |
TotalEnergyConsumed | Energy consumed from OEM SCADA counter | SCADA | |
Voltage | Real time average voltage measured from Inverter | SCADA | |
VoltageA | Real time voltage in phase A measured from Inverter | SCADA | |
VoltageB | Real time voltage in phase B measured from Inverter | SCADA | |
VoltageC | Real time voltage in phase C measured from Inverter | SCADA | |
Irradiance | Irradiance from configured reference weatherstation | SCADA | |
IrradianceRear | Rear Irradiance from configured referenced weatherstation - required for bifacial modules. | SCADA | |
CommunicationState | Scale Equation | ||
IEC-OperationState | Scale Equation | ||
ApparentPower | Apparent power measured from Inverter | SCADA | |
SetpointActivePower | Inverter Active Power Setpoint – Output/Limit | SCADA | |
SetpointActivePowerCMD | Inverter Active Power Setpoint command as the ratio of nominal inverter capacity [0-1] | SCADA | |
TempPanel | Weather Station panel temperature sensor average for Inverter Asset (mapped via source tag) | SCADA |