The Core Real-Time Data is a Certified Product Point Template for Battery Containers that defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all battery containers. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio.

This point template provides a reliable baseline of real-time data expected from each Battery Container modeled in Bazefield. The purpose is to:

  • Ensure consistent naming and normalization of critical telemetry available on all makes and models of battery containers

  • Streamline configuration for SCADA or historian data ingestion

  • Support cross-site and cross-technology data normalization

The Core Real-Time Data template defines 24 standard data streams for Battery Containers. Battery Containers represent the physical battery enclosures that house one or more battery racks/strings connected to a Power Conversion System.

Template Definition

The Core Real-Time Data template contains standard data streams for Battery Container SCADA data. Details on the Point Names, Descriptions, and Types are below. The Core Real-Time Data template specifically holds all the critical “raw” data expected from all Battery Container SCADA systems.

Minimum Requirements: In most modern battery containers, there will be a significant number of points available beyond this list which are vendor or SCADA specific. This list represents the minimum, common list of critical data often available in ALL vendors and SCADA systems. Many of the points below are used directly in Bazefield core functionality, or core performance calculations.

Required for Bazefield Core Dashboard functionality

Optional for common additional data streams/sources

Point Definition Table

Name

Description

Type

Unit

CellTempAvg

Average temperature of cells in the container

Raw Data

°C

CellTempMax

Maximum cell temperature in the container

Raw Data

°C

CellTempMin

Minimum cell temperature in the container

Raw Data

°C

CellVoltageAvg

Average voltage of cells in the container

Raw Data

V

CellVoltageMax

Maximum cell voltage in the container

Raw Data

V

CellVoltageMin

Minimum cell voltage in the container

Raw Data

V

ChargeCurrentMax

Instantaneous maximum DC charge current.

Raw Data

A

DC-Current

Total DC current flowing to/from battery container

Raw Data

A

DC-Power

Total power flowing to/from battery container

Raw Data

kW

DC-Voltage

Total DC Voltage on the container

Raw Data

V

DischargeCurrentMax

Instantaneous maximum DC discharge current.

Raw Data

A

PowerChargeLimit

DC Chargeable Power Limit

Raw Data

kW

PowerDischargeLimit

DC Dischargeable Power Limit

Raw Data

kW

RackCurrentAvg

Average string/rack current for all strings/racks in the container

Raw Data

A

RackCurrentMax

Maximum current of any rack/string in the container

Raw Data

A

RackCurrentMin

Minimum current of any rack/string in the container

Raw Data

A

RackVoltageAvg

Average string/rack voltage for all strings/racks in the container

Raw Data

V

RackVoltageMax

Maximum rack/string voltage for all racks/strings in the container

Raw Data

V

RackVoltageMin

Minimum rack/string voltage for all racks/strings in the container

Raw Data

V

StateOfCharge

Amount of charge in the container, expressed as a percentage

Raw Data

%

StateOfChargeMaxLimit

Maximum State of Charge Limit

Raw Data

%

StateOfChargeMinLimit

Minimum State of Charge Limit

Raw Data

%

StateOfHealth

State of Health (SOH)

Raw Data

%

TempInternal

Internal container ambient air temperature. Distinct from cell temperatures — used for thermal management and HVAC diagnostics.

Raw Data

°C