Overview
The Core PCS Enclosure Data is an optional Certified Product Point Template for Power Conversion Systems. It should only be applied to integrated single-unit BESS — systems where the inverter and battery enclosure are combined into a single physical unit, such as the Tesla Megapack. Do not apply this template to traditional PCS assets where battery containers are modeled separately.
In a standard ESS architecture, battery-level DC measurements (rack currents, voltages, SOC limits) are collected on the Battery Container or Battery Rack objects. For single-unit systems where the inverter and container are inseparable, those same measurements surface at the PCS level — this template captures them there.
When to deploy: Apply Core PCS Enclosure Data only when the PCS object represents a combined inverter + battery enclosure (e.g. Tesla Megapack, similar integrated BESS products). Do not apply it alongside a separate Battery Container hierarchy for the same physical unit.
Template Definition
The Core PCS Enclosure Data template defines 12 DC-side and enclosure-level data streams for integrated single-unit BESS modeled as a PCS. These points capture DC current/voltage limits, rack-level measurements, and State of Health data that are only available at the PCS level when no separate Battery Container object exists.
Required for Bazefield Core Dashboard functionality
Optional for common additional data streams/sources
Point Definition Table
Name | Description | Type | Unit | |
|---|---|---|---|---|
ChargeCurrentMax | Instantaneous maximum DC charge current | Raw Data | A | |
DischargeCurrentMax | Instantaneous maximum DC discharge current | Raw Data | A | |
RackCurrentAvg | Average string/rack current within the enclosure | Raw Data | A | |
RackCurrentMax | Maximum string/rack current within the enclosure | Raw Data | A | |
RackCurrentMin | Minimum string/rack current within the enclosure | Raw Data | A | |
RackVoltageAvg | Average string/rack voltage within the enclosure | Raw Data | V | |
RackVoltageMax | Maximum string/rack voltage within the enclosure | Raw Data | V | |
RackVoltageMin | Minimum string/rack voltage within the enclosure | Raw Data | V | |
StateOfChargeMaxLimit | Maximum State of Charge operating limit | Raw Data | % | |
StateOfChargeMinLimit | Minimum State of Charge operating limit | Raw Data | % | |
StateOfHealth | State of Health (SOH) of the PCS's connected battery system. Represents aggregate battery degradation. | Raw Data | % | |
TempInternal | Internal enclosure ambient air temperature. For integrated single-unit systems (e.g. Tesla Megapack) modeled as PCS. | Raw Data | °C |