Core OEM SQL Data

Prev Next

Overview

The Core OEM SQL Data is a Certified Product Point Template for Wind Turbines defines optional telemetry Bazefield recommends for advanced analysis of 10-minute data sets often provided by Wind Turbine OEM SCADA systems. These points are not required for monitoring but can be helpful for more accurate month-end reporting, and situations where data coverage and quality is critical to the end-user.  It is meant to compliment much of the OPC data found in the Core Real-Time Data template.

Template Definition

The Core OEM SQL template specifically holds all the critical “raw” pre-aggregated 10-minute data expected from most Wind Turbine SCADA systems.  Specifically, it is common for many vendors of wind turbines to host an on-site SQL database with localized schema for the below points.  Bazefield supports interfaces to all major OEM SQL databases to map OEM definitions and namespaces of the below points to the normalized point names provided in the table.  

Minimum Requirements

In most modern wind turbines, there will be a significant number points available beyond this list which are vendor or SCADA specific.  This list represents the minimum, common list of critical data often available in ALL vendors and SCADA systems.  

Details on the Point Names, Descriptions, and Types are below.

Required for Bazefield Core Dashboard functionality

Optional for common additional data streams/sources

Name

Description

Type

Unit

ActivePower.10m

Active power of wind turbine, from ODBC SQL Historian

SCADA (SQL)

kW

AmbientTemperature.10m

Ambient temperature, from ODBC SQL Historian

SCADA (SQL)

o

Blade_PitchAngle.10m

Avg pitch angle of all three blades from ODBC SQL Historian

SCADA (SQL)

o

Blade1_PitchAngle.10m

Pitch angle of first blade from ODBC SQL Historian

SCADA (SQL)

o

Blade2_PitchAngle.10m

Pitch angle of second blade from ODBC SQL Historian

SCADA (SQL)

o

Blade3_PitchAngle.10m

Pitch angle of third blade from ODBC SQL Historian

SCADA (SQL)

o

Current.10m

Voltage, from ODBC SQL Historian

SCADA (SQL)

A

CurrentA.10m

Current in phase A, from ODBC SQL Historian

SCADA (SQL)

A

CurrentB.10m

Current in phase B, from ODBC SQL Historian

SCADA (SQL)

A

CurrentC.10m

Current in phase C, from ODBC SQL Historian

SCADA (SQL)

A

ErrorCode.10m

Error code (single tag) for OEM vendor at end of interval, from ODBC SQL Historian

SCADA (SQL)

--

Frequency.10m

Grid frequency in Hz, from ODBC SQL Historian

SCADA (SQL)

Hz

GeneratorSpeed.10m

Generator speed in RPM, typically from the OPC interface

SCADA (SQL)

RPM

NacelleDirection.10m

Nacelle direction, from ODBC SQL Historian

SCADA (SQL)

o

OperationState.10m

Native operating state for the WTG, from ODBC SQL Historian

SCADA (SQL)

--

PowerFactor.10m

Power factor, typically from ODBC SQL Historian

SCADA (SQL)

%

ReactivePower.10m

Reactive power of wind turbine, from ODBC SQL Historian

SCADA (SQL)

kVar

RotorSpeed.10m

Rotor speed in RPM, typically from the OPC interface

SCADA (SQL)

RPM

TotalEnergyConsumed.10m

Lifetime energy consumed counter at end of interval, from ODBC SQL Historian

SCADA (SQL)

kWh

TotalEnergyProduced.10m

Lifetime energy produced counter at end of interval, from ODBC SQL Historian

SCADA (SQL)

kWh

Voltage.10m

Current, from ODBC SQL Historian

SCADA (SQL)

V

VoltageA.10m

Voltage in phase A, from ODBC SQL Historian

SCADA (SQL)

V

VoltageB.10m

Voltage in phase B, from ODBC SQL Historian

SCADA (SQL)

V

VoltageC.10m

Voltage in phase C, from ODBC SQL Historian

SCADA (SQL)

V

WindDirection.10m

Absolute wind direction from wind vane measurement, from ODBC SQL Historian

SCADA (SQL)

o

WindSpeed.10m

Nacelle wind speed of wind turbine (primary anemombeter), from ODBC SQL Historian

SCADA (SQL)

m/s