Overview
The Core Real-Time Data is a Certified Product Point Template for Wind Turbines defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all wind turbines. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio.
This point template provides a reliable baseline of real-time data expected from each Wind Turbine modeled in Bazefield. The purpose is to:
Ensure consistent naming and normalization of critical telemetry available on all makes and models of wind turbines
Streamline configuration for SCADA or historian data ingestion
Support cross-site and cross-technology data normalization
Template Definition
The Core Real-Time Data template contains standard data streams for turbine SCADA data. Details on the Point Names, Descriptions, and Types are below. The Core Real-TIme Data template specifically holds all the critical “raw” data expected from all wind turbine SCADA systems. For wind turbines, the core-real time data points are often provided directly from an OPC server provided by the OEM of the wind turbine.
Minimum Requirements
In most modern wind turbines, there will be a significant number points available beyond this list which are vendor or SCADA specific. This list represents the minimum, common list of critical data often available in ALL vendors and SCADA systems. Many of the points below are used directly in Bazefield core functionality, or core performance calculations.
Required for Bazefield Core Dashboard functionality
Optional for common additional data streams/sources
Name | Description | Type | Unit | |
---|---|---|---|---|
ActivePower | Active power measured from turbine | SCADA (raw) | kW | |
AmbientTemperature | Ambient temperature measured from turbine | SCADA (raw) | o C | |
Blade_PitchAngle | Average Pitch Angle of all 3 blades | SCADA (raw) | o | |
Blade1_PitchAngle | Pitch angle of blade 1 | SCADA (raw) | o | |
Blade2_PitchAngle | Pitch angle of blade 2 | SCADA (raw) | o | |
Blade3_PitchAngle | Pitch angle of blade 3 | SCADA (raw) | o | |
Current | Real time current measured from turbine | SCADA (raw) | A | |
CurrentA | Real time current in phase A, typically from OPC interface | SCADA (raw) | A | |
CurrentB | Real time current in phase B, typically from OPC interface | SCADA (raw) | A | |
CurrentC | Real time current in phase C, typically from OPC interface | SCADA (raw) | A | |
ErrorCode | Real time error code (single tag) for OEM vendor, typically from an OPC interface | SCADA (raw) | -- | |
Frequency | Real time frequency in Hz measured from turbine | SCADA (raw) | Hz | |
GeneratorSpeed | Generator speed measured from turbine | SCADA (raw) | RPM | |
NacelleDirection | Nacelle direction measured from turbine (absolute) | SCADA (raw) | o | |
OperationState | Operating state for the WTG, typically from an OPC interface | SCADA (raw) | -- | |
PowerFactor | Real time power factor measured from turbine | SCADA (raw) | % | |
ReactivePower | Reactive power measured from tubrine | SCADA (raw) | kVar | |
RotorSpeed | Rotor speed measured form turbine | SCADA (raw) | RPM | |
SetpointActivePower | Real time active power setpoint provided to turbine from power plant controller | SCADA (raw) | kW | |
SetpointActivePowerPercent | Real time active power setpoint relative to the rated power of the machine | SCADA (raw) | % | |
TotalEnergyConsumed | Energy consumed from OEM SCADA counter | SCADA (raw) | kWh | |
TotalEnergyProduced | Energy produced from the OEM SCADA counter | SCADA (raw) | kWh | |
Voltage | Real time average voltage measured from turbine | SCADA (raw) | V | |
VoltageA | Real time voltage in phase A measured from turbine | SCADA (raw) | V | |
VoltageB | Real time voltage in phase B measured from turbine | SCADA (raw) | V | |
VoltageC | Real time voltage in phase C measured from turbine | SCADA (raw) | V | |
WindDirection | Wind direction measured from turbine (absolute reference) | SCADA (raw) | o | |
WindSpeed | Raw Nacelle Wind speed measured from turbine | SCADA (raw) | m/s |