Core Real-Time Data (DC)

Prev Next

Overview

The Core Real-Time Data is a Certified Product Point Template for PV Inverters which defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all solar inverters. The measurements in this template are at the Direct Current (DC) level. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio.

This point template provides a reliable baseline of real-time data expected from each PV Inverter modeled in Bazefield. The purpose is to:

  • Ensure consistent naming and normalization of critical telemetry available on all makes and models of PV Inverters

  • Streamline configuration for SCADA or historian data ingestion

  • Support cross-site and cross-technology data normalization

Template Definition

The Core Real-Time Data template contains standard data streams for inverter SCADA data, specifically DC electrical measurements. The included DC Zone Currents may be modelled on the DC Combiner objects directly, if they are used in the Object Manager hierarchy. Details on the Point Names, Descriptions, and Types are below.  The Core Real-TIme Data template specifically holds all the critical “raw” data expected from all solar inverter SCADA systems.  For solar inverters, the core-real time data points are often provided directly from an Modbus TCP interface provided by the OEM of the solar inverter.

Minimum Requirements

In most modern solar inverters, there will be a significant number points available beyond this list which are vendor or SCADA specific.  This list represents the minimum, common list of critical data often available in ALL vendors and SCADA systems.  Many of the points below are used directly in Bazefield core functionality, or core performance calculations.

Required for Bazefield Core Dashboard functionality

Optional for common additional data streams/sourcesOverview

Name

Description

Type

DC-Current

Inverter DC Current Total (A DC)

SCADA (raw)

DC-Power

Inverter DC Power (kW DC)

SCADA (raw)

DC-Voltage

Inverter DC Voltage (V DC)

SCADA (raw)

DCZone-Current01

Inverter Zone/Recombiner Input 1 DC Current (A DC)

SCADA (raw)

DCZone-Current02

Inverter Zone/Recombiner Input 2 DC Current (A DC)

SCADA (raw)

DCZone-Current03

Inverter Zone/Recombiner Input 3 DC Current (A DC)

SCADA (raw)

DCZone-Current04

Inverter Zone/Recombiner Input 4 DC Current (A DC)

SCADA (raw)

DCZone-Current05

Inverter Zone/Recombiner Input 5 DC Current (A DC)

SCADA (raw)

DCZone-Current06

Inverter Zone/Recombiner Input 6 DC Current (A DC)

SCADA (raw)

DCZone-Current07

Inverter Zone/Recombiner Input 7 DC Current (A DC)

SCADA (raw)

DCZone-Current08

Inverter Zone/Recombiner Input 8 DC Current (A DC)

SCADA (raw)

DCZone-Current09

Inverter Zone/Recombiner Input 9 DC Current (A DC)

SCADA (raw)

DCZone-Current10

Inverter Zone/Recombiner Input 10 DC Current (A DC)

SCADA (raw)

DCZone-Current11

Inverter Zone/Recombiner Input 11 DC Current (A DC)

SCADA (raw)

DCZone-Current12

Inverter Zone/Recombiner Input 12 DC Current (A DC)

SCADA (raw)

DCZone-Current13

Inverter Zone/Recombiner Input 13 DC Current (A DC)

SCADA (raw)

DCZone-Current14

Inverter Zone/Recombiner Input 14 DC Current (A DC)

SCADA (raw)

DCZone-Current15

Inverter Zone/Recombiner Input 15 DC Current (A DC)

SCADA (raw)

DCZone-Current16

Inverter Zone/Recombiner Input 16 DC Current (A DC)

SCADA (raw)

DCZone-Current17

Inverter Zone/Recombiner Input 17 DC Current (A DC)

SCADA (raw)

DCZone-Current18

Inverter Zone/Recombiner Input 18 DC Current (A DC)

SCADA (raw)

DCZone-Current19

Inverter Zone/Recombiner Input 19 DC Current (A DC)

SCADA (raw)

DCZone-Current20

Inverter Zone/Recombiner Input 20 DC Current (A DC)

SCADA (raw)

DCZone-Current21

Inverter Zone/Recombiner Input 21 DC Current (A DC)

SCADA (raw)

DCZone-Current22

Inverter Zone/Recombiner Input 22 DC Current (A DC)

SCADA (raw)

DCZone-Current23

Inverter Zone/Recombiner Input 23 DC Current (A DC)

SCADA (raw)

DCZone-Current24

Inverter Zone/Recombiner Input 24 DC Current (A DC)

SCADA (raw)

DCZone-Current25

Inverter Zone/Recombiner Input 25 DC Current (A DC)

SCADA (raw)

DCZone-Current26

Inverter Zone/Recombiner Input 26 DC Current (A DC)

SCADA (raw)

DCZone-Current27

Inverter Zone/Recombiner Input 27 DC Current (A DC)

SCADA (raw)

DCZone-Current28

Inverter Zone/Recombiner Input 28 DC Current (A DC)

SCADA (raw)

DCZone-Current29

Inverter Zone/Recombiner Input 29 DC Current (A DC)

SCADA (raw)

DCZone-Current30

Inverter Zone/Recombiner Input 30 DC Current (A DC)

SCADA (raw)

DCZone-Current31

Inverter Zone/Recombiner Input 31 DC Current (A DC)

SCADA (raw)

DCZone-Current32

Inverter Zone/Recombiner Input 32 DC Current (A DC)

SCADA (raw)

DC-Current1

Inverter MPPT [1] DC Current (A DC)

SCADA (raw)

DC-Current2

Inverter MPPT [2] DC Current (A DC)

SCADA (raw)

DC-Current3

Inverter MPPT [3] DC Current (A DC)

SCADA (raw)

DC-Current4

Inverter MPPT [4] DC Current (A DC)

SCADA (raw)

DC-Current5

Inverter MPPT [5] DC Current (A DC)

SCADA (raw)

DC-Current6

Inverter MPPT [6] DC Current (A DC)

SCADA (raw)

DC-Current7

Inverter MPPT [7] DC Current (A DC)

SCADA (raw)

DC-Current8

Inverter MPPT [8] DC Current (A DC)

SCADA (raw)

DC-Current9

Inverter MPPT [9] DC Current (A DC)

SCADA (raw)

DC-Current10

Inverter MPPT [10] DC Current (A DC)

SCADA (raw)

DC-Current11

Inverter MPPT [11] DC Current (A DC)

SCADA (raw)

DC-Current12

Inverter MPPT [12] DC Current (A DC)

SCADA (raw)

DC-Current13

Inverter MPPT [13] DC Current (A DC)

SCADA (raw)

DC-Current14

Inverter MPPT [14] DC Current (A DC)

SCADA (raw)

DC-Current15

Inverter MPPT [15] DC Current (A DC)

SCADA (raw)

DC-Current16

Inverter MPPT [16] DC Current (A DC)

SCADA (raw)

DC-Voltage1

Inverter MPPT [1] Voltage (V DC)

SCADA (raw)

DC-Voltage2

Inverter MPPT [2] Voltage (V DC)

SCADA (raw)

DC-Voltage3

Inverter MPPT [3] Voltage (V DC)

SCADA (raw)

DC-Voltage4

Inverter MPPT [4] Voltage (V DC)

SCADA (raw)

DC-Voltage5

Inverter MPPT [5] Voltage (V DC)

SCADA (raw)

DC-Voltage6

Inverter MPPT [6] Voltage (V DC)

SCADA (raw)

DC-Voltage7

Inverter MPPT [7] Voltage (V DC)

SCADA (raw)

DC-Voltage8

Inverter MPPT [8] Voltage (V DC)

SCADA (raw)

DC-Voltage9

Inverter MPPT [9] Voltage (V DC)

SCADA (raw)

DC-Voltage10

Inverter MPPT [10] Voltage (V DC)

SCADA (raw)

DC-Voltage11

Inverter MPPT [11] Voltage (V DC)

SCADA (raw)

DC-Voltage12

Inverter MPPT [12] Voltage (V DC)

SCADA (raw)

DC-Voltage13

Inverter MPPT [13] Voltage (V DC)

SCADA (raw)

DC-Voltage14

Inverter MPPT [14] Voltage (V DC)

SCADA (raw)

DC-Voltage15

Inverter MPPT [15] Voltage (V DC)

SCADA (raw)

DC-Voltage16

Inverter MPPT [16] Voltage (V DC)

SCADA (raw)