Core Monitoring KPIs

Prev Next

Overview

The Core Monitoring KPIs is a Certified Product Point Template for Energy Storage Sites that defines required normalized real-time performance calculations that scale, or transform several of the points in the Core Real-Time Calculations. These points are required for the Bazefield installation to function properly across all core applications.

These calculations specifically translate OEM-specific signals into consistent indicators of operational state, availability, communication status, and event conditions. By abstracting vendor-specific complexities, the Core Monitoring KPIs enables unified fleet monitoring, reduces configuration overhead, and supports consistent reporting and alarm management across heterogeneous energy storage sites technologies.

The Core Monitoring KPIs template defines 19 interval-based calculations for Energy Storage Sites. These KPIs aggregate PCS and Container metrics into site-level 5-minute and hourly summaries for power production, energy throughput, state of charge, and data quality.

Template Definition

The Core Monitoring KPIs is defined below. Calculations are one of the following types:

  • Scale Equations — Algebraic or logical manipulations of input data done on the Bazefield edge buffer

  • Online Expressions — Algebraic or logical manipulations of input data done on the central Bazefield data engines (typically on a storage node). Similar to scale equations in purpose, but done in the centralized architecture.

  • Interval Expressions — Algebraic, logical, or advanced manipulations of input data done within a pre-defined aggregation interval (e.g. 5 minutes, 10 minutes, 1 hour, etc). These are typically done centrally on a storage node.

Details on the Point Names, Descriptions, and Types are below.

Required for Bazefield Core Dashboard functionality

Optional for common additional data streams/sources

Calculation Definition Table

Name

Description

Type

Interval

Units

ACDataCoverage

Site-level average of PCS AC Power data coverage for the hour

Calculation (Interval Exp.)

1 hour

%

ActivePowerPCS

Sum of battery inverter Active Power in MW

Calculation (Interval Exp.)

5 min

MW

ChargingEnergy

Sum of energy charged to containers

Calculation (Interval Exp.)

5 min

MWh

ChargingPower

Calculated value of power input while charging

Calculation (Interval Exp.)

5 min

MW

ContainerSOCDataCoverage

Site-level average of Container State of Charge data coverage for the hour

Calculation (Interval Exp.)

1 hour

%

DCDataCoverage

Site-level average of Container DC Power data coverage for the hour

Calculation (Interval Exp.)

1 hour

%

DifferentialEnergy

Difference between energy charged and discharged in past hour

Calculation (Interval Exp.)

1 hour

MWh

DischargingEnergy

Sum of energy discharged from containers

Calculation (Interval Exp.)

5 min

MWh

DischargingPower

Calculated value of power output while discharging

Calculation (Interval Exp.)

5 min

MW

EquivalentFullCycles

Hourly equivalent full cycles. Total energy throughput (charged + discharged) divided by 2 and normalized by rated energy capacity. Requires capacity attribute.

Calculation (Interval Exp.)

1 hour

HourlyEnergyCharged

Site-level hourly total energy charged, summed from PCS units

Calculation (Interval Exp.)

1 hour

MWh

HourlyEnergyDischarged

Site-level hourly total energy discharged, summed from PCS units

Calculation (Interval Exp.)

1 hour

MWh

OverallDataQuality

Hourly site-level overall data quality score as equal-weighted average of AC Power, State of Charge, DC Power, and Container SOC data coverage

Calculation (Interval Exp.)

1 hour

%

PowerChargeLimit

Site Power Charge Limit calculated as sum of all battery containers' Power Charge Limit

Calculation (Interval Exp.)

5 min

MW

PowerDischargeLimit

Site Power Discharge Limit calculated as sum of all battery containers' Power Discharge Limit

Calculation (Interval Exp.)

5 min

MW

ReactivePowerPCS

Sum of battery inverter Reactive Power in MVAR

Calculation (Interval Exp.)

5 min

MVAR

SOCDataCoverage

Site-level average of PCS State of Charge data coverage for the hour

Calculation (Interval Exp.)

1 hour

%

StateOfChargeAvg

Average State Of Charge of the Site

Calculation (Interval Exp.)

5 min

%

TotalStoredEnergy

Site total stored energy across all battery containers

Calculation (Interval Exp.)

5 min

MWh