--- title: "Core Real-Time Data" slug: "core-real-time-data-circuit" updated: 2025-11-04T17:59:33Z published: 2025-11-04T18:00:40Z canonical: "docs.bazefield.com/core-real-time-data-circuit" --- > ## Documentation Index > Fetch the complete documentation index at: https://docs.bazefield.com/llms.txt > Use this file to discover all available pages before exploring further. # Core Real-Time Data ### Overview The *Core Real-Time Data* is a Certified Product Point Template for [Circuit](/product/docs/circuit) which defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all [Circuits](/product/docs/circuit). These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio. This point template provides a reliable baseline of real-time data expected from each [Circuit](/product/docs/circuit) modeled in Bazefield. The purpose is to: - Ensure consistent naming and normalization of critical telemetry available on all makes and models of [Circuits](/product/docs/circuit) - Streamline configuration for SCADA or historian data ingestion - Support cross-site and cross-technology data normalization ### Template Definition The [*Core Real-Time Data*](/product/docs/core-real-time-data-circuit#overview) point template includes telemetry definitions for standard circuit measurements and aggregates. Circuit data is optional, and it not required for Bazefield Core needs. Details on the Point Names, Descriptions, and Types are below. Required for Bazefield Core Dashboard functionality Optional for common additional data streams/sources | Name | Description | Type | Interval | Units | | | --- | --- | --- | --- | --- | --- | | ActivePower | Calculated Data: Sum of inverter active power | Calculation (Interval Exp.) | 300 s | kW | | | AssetsAvailable | Calculated Data: Number of assets available | Calculation (Online Exp.) | Real-Time | | | | AssetsNumber | Number of assets under the Circuit | Calculation (Online Exp.) | Real-Time | | | | BreakerStatus | 0 = breaker closed; 1 = breaker open | Scale Equation | Real-Time | | | | PerformanceIndex | Calculated Data: Circuit Performance Index | Calculation (Interval Exp.) | 300 s | % | |