--- title: "Inverter Calculated Events" slug: "inverter-calculated-events" updated: 2025-10-23T17:34:54Z published: 2025-10-23T17:34:54Z canonical: "docs.bazefield.com/inverter-calculated-events" --- > ## Documentation Index > Fetch the complete documentation index at: https://docs.bazefield.com/llms.txt > Use this file to discover all available pages before exploring further. # Inverter Calculated Events ## Overview The *Inverter Calculated Events* is a Certified Product Event Template for [PV Inverters](/product/docs/pv-inverter) that defines standard process data-based [events](/product/docs/events). This template enables automatic event creation based on operational states and performance conditions, ensuring accurate reliability and availability reporting across your portfolio. Inverter Calculated Events can be used to streamline compliance reporting, and provide a consistent foundation for outage and derate tracking. This event template provides a set of standardized calculated events derived from inverter telemetry and operational logic. The purpose is to: - Ensure consistent naming and normalization of calculated events across all makes and models of [inverters](/product/docs/pv-inverter) - Support cross-site and cross-technology data normalization for compliance reporting - Enable automatic event creation based on process data triggers for improved accuracy and efficiency These events can be used to determine Inverter hours according to IEC standards. In the Americas, these events are used directly in Bazefield’s automatic report generation for NERC GADS (Generating Availability Data System) performance and event reporting for [Solar Farms](/product/docs/solar-farm). If OEM specific alarms and states are available, they can be used instead of or in tandem with this template. ## Template Definition The [Inverter Calculated Events](/product/docs/inverter-gads-events#overview) template contains standard calculated events for inverter operational states, based on inverter and environmental conditions. Details on the Event Codes, Names, Descriptions, Types, and Remarks are provided below. Required for Bazefield Core Dashboard functionality Optional for common additional data sources | Code | Name | Description | Type | Remarks | | | --- | --- | --- | --- | --- | --- | | 10000 | EVENT-DaylightHours | Sunrise: Daylight Hours | Info | Bazefield calculation of expected Sunrise and daylight hours based on latitude and longitude of inverter | | | 10001 | EVENT-NightHours | Sunset: Night Hours | Info | Bazefield calculation of Expected sunset based on latitude and longitude of inverter | | | 10003 | EVENT-Generating | AC Generating | Info | Bazefield calculation flagging when the machine is producing positive active AC Power | | | 10004 | EVENT-LowIrradiancePOA-Day | Low Irradiance: Day | Info | Irradiance is below threshold during daylight hours | | | 10005 | EVENT-NonGenDay-LowIrr | Non Gen, Low Irradiance: Day | Info | Inverter is stopped due to low irradiance during the day | | | 10006 | EVENT-NonGenNight-LowIrr | Non Gen, Low Irradiance: Night | Info | Inverter is stopped due to low irradiance during night hours | | | 10007 | EVENT-LowIrradiancePOA-Night | Low Irradiance: Night | Info | Irradiance is below threshold and it is night hours | | | 10008 | EVENT-NotGenerating | Not Generating | Alarm | Inverter has stopped generating during the daylight hours. | | ``