--- title: "Core Real-Time Data (DC)" slug: "core-real-time-data-dc-inverter" updated: 2025-10-24T19:30:44Z published: 2025-10-24T19:30:44Z canonical: "docs.bazefield.com/core-real-time-data-dc-inverter" --- > ## Documentation Index > Fetch the complete documentation index at: https://docs.bazefield.com/llms.txt > Use this file to discover all available pages before exploring further. # Core Real-Time Data (DC) ## Overview The *Core Real-Time Data* is a Certified Product Point Template for [PV Inverters](/product/docs/pv-inverter) which defines the standardized, minimum set of telemetry (e.g. time series points) Bazefield recommends for real-time monitoring of all solar inverters. The measurements in this template are at the Direct Current (DC) level. These points ensure consistent data collection, improve interoperability across assets, and enable accurate reporting and analysis across your portfolio. This point template provides a reliable baseline of real-time data expected from each [PV Inverter](/product/docs/pv-inverter) modeled in Bazefield. The purpose is to: - Ensure consistent naming and normalization of critical telemetry available on all makes and models of [PV Inverters](/product/docs/pv-inverter) - Streamline configuration for SCADA or historian data ingestion - Support cross-site and cross-technology data normalization ## Template Definition The Core Real-Time Data template contains standard data streams for inverter SCADA data, specifically DC electrical measurements. The included DC Zone Currents may be modelled on the DC Combiner objects directly, if they are used in the Object Manager hierarchy. Details on the Point Names, Descriptions, and Types are below. The *Core Real-TIme Data* template specifically holds all the critical “raw” data expected from all solar inverter SCADA systems. For solar inverters, the core-real time data points are often provided **directly from an Modbus TCP interface** provided by the OEM of the solar inverter. > [!NOTE] > Minimum Requirements > > In most modern solar inverters, there will be a significant number points available beyond this list which are vendor or SCADA specific. This list represents the minimum, common list of critical data often available in ALL vendors and SCADA systems. Many of the points below are used directly in Bazefield core functionality, or core performance calculations. Required for Bazefield Core Dashboard functionality Optional for common additional data streams/sourcesOverview | Name | Description | Type | | | --- | --- | --- | --- | | DC-Current | Inverter DC Current Total (A DC) | SCADA (raw) | | | DC-Power | Inverter DC Power (kW DC) | SCADA (raw) | | | DC-Voltage | Inverter DC Voltage (V DC) | SCADA (raw) | | | DCZone-Current01 | Inverter Zone/Recombiner Input 1 DC Current (A DC) | SCADA (raw) | | | DCZone-Current02 | Inverter Zone/Recombiner Input 2 DC Current (A DC) | SCADA (raw) | | | DCZone-Current03 | Inverter Zone/Recombiner Input 3 DC Current (A DC) | SCADA (raw) | | | DCZone-Current04 | Inverter Zone/Recombiner Input 4 DC Current (A DC) | SCADA (raw) | | | DCZone-Current05 | Inverter Zone/Recombiner Input 5 DC Current (A DC) | SCADA (raw) | | | DCZone-Current06 | Inverter Zone/Recombiner Input 6 DC Current (A DC) | SCADA (raw) | | | DCZone-Current07 | Inverter Zone/Recombiner Input 7 DC Current (A DC) | SCADA (raw) | | | DCZone-Current08 | Inverter Zone/Recombiner Input 8 DC Current (A DC) | SCADA (raw) | | | DCZone-Current09 | Inverter Zone/Recombiner Input 9 DC Current (A DC) | SCADA (raw) | | | DCZone-Current10 | Inverter Zone/Recombiner Input 10 DC Current (A DC) | SCADA (raw) | | | DCZone-Current11 | Inverter Zone/Recombiner Input 11 DC Current (A DC) | SCADA (raw) | | | DCZone-Current12 | Inverter Zone/Recombiner Input 12 DC Current (A DC) | SCADA (raw) | | | DCZone-Current13 | Inverter Zone/Recombiner Input 13 DC Current (A DC) | SCADA (raw) | | | DCZone-Current14 | Inverter Zone/Recombiner Input 14 DC Current (A DC) | SCADA (raw) | | | DCZone-Current15 | Inverter Zone/Recombiner Input 15 DC Current (A DC) | SCADA (raw) | | | DCZone-Current16 | Inverter Zone/Recombiner Input 16 DC Current (A DC) | SCADA (raw) | | | DCZone-Current17 | Inverter Zone/Recombiner Input 17 DC Current (A DC) | SCADA (raw) | | | DCZone-Current18 | Inverter Zone/Recombiner Input 18 DC Current (A DC) | SCADA (raw) | | | DCZone-Current19 | Inverter Zone/Recombiner Input 19 DC Current (A DC) | SCADA (raw) | | | DCZone-Current20 | Inverter Zone/Recombiner Input 20 DC Current (A DC) | SCADA (raw) | | | DCZone-Current21 | Inverter Zone/Recombiner Input 21 DC Current (A DC) | SCADA (raw) | | | DCZone-Current22 | Inverter Zone/Recombiner Input 22 DC Current (A DC) | SCADA (raw) | | | DCZone-Current23 | Inverter Zone/Recombiner Input 23 DC Current (A DC) | SCADA (raw) | | | DCZone-Current24 | Inverter Zone/Recombiner Input 24 DC Current (A DC) | SCADA (raw) | | | DCZone-Current25 | Inverter Zone/Recombiner Input 25 DC Current (A DC) | SCADA (raw) | | | DCZone-Current26 | Inverter Zone/Recombiner Input 26 DC Current (A DC) | SCADA (raw) | | | DCZone-Current27 | Inverter Zone/Recombiner Input 27 DC Current (A DC) | SCADA (raw) | | | DCZone-Current28 | Inverter Zone/Recombiner Input 28 DC Current (A DC) | SCADA (raw) | | | DCZone-Current29 | Inverter Zone/Recombiner Input 29 DC Current (A DC) | SCADA (raw) | | | DCZone-Current30 | Inverter Zone/Recombiner Input 30 DC Current (A DC) | SCADA (raw) | | | DCZone-Current31 | Inverter Zone/Recombiner Input 31 DC Current (A DC) | SCADA (raw) | | | DCZone-Current32 | Inverter Zone/Recombiner Input 32 DC Current (A DC) | SCADA (raw) | | | DC-Current1 | Inverter MPPT [1] DC Current (A DC) | SCADA (raw) | | | DC-Current2 | Inverter MPPT [2] DC Current (A DC) | SCADA (raw) | | | DC-Current3 | Inverter MPPT [3] DC Current (A DC) | SCADA (raw) | | | DC-Current4 | Inverter MPPT [4] DC Current (A DC) | SCADA (raw) | | | DC-Current5 | Inverter MPPT [5] DC Current (A DC) | SCADA (raw) | | | DC-Current6 | Inverter MPPT [6] DC Current (A DC) | SCADA (raw) | | | DC-Current7 | Inverter MPPT [7] DC Current (A DC) | SCADA (raw) | | | DC-Current8 | Inverter MPPT [8] DC Current (A DC) | SCADA (raw) | | | DC-Current9 | Inverter MPPT [9] DC Current (A DC) | SCADA (raw) | | | DC-Current10 | Inverter MPPT [10] DC Current (A DC) | SCADA (raw) | | | DC-Current11 | Inverter MPPT [11] DC Current (A DC) | SCADA (raw) | | | DC-Current12 | Inverter MPPT [12] DC Current (A DC) | SCADA (raw) | | | DC-Current13 | Inverter MPPT [13] DC Current (A DC) | SCADA (raw) | | | DC-Current14 | Inverter MPPT [14] DC Current (A DC) | SCADA (raw) | | | DC-Current15 | Inverter MPPT [15] DC Current (A DC) | SCADA (raw) | | | DC-Current16 | Inverter MPPT [16] DC Current (A DC) | SCADA (raw) | | | DC-Voltage1 | Inverter MPPT [1] Voltage (V DC) | SCADA (raw) | | | DC-Voltage2 | Inverter MPPT [2] Voltage (V DC) | SCADA (raw) | | | DC-Voltage3 | Inverter MPPT [3] Voltage (V DC) | SCADA (raw) | | | DC-Voltage4 | Inverter MPPT [4] Voltage (V DC) | SCADA (raw) | | | DC-Voltage5 | Inverter MPPT [5] Voltage (V DC) | SCADA (raw) | | | DC-Voltage6 | Inverter MPPT [6] Voltage (V DC) | SCADA (raw) | | | DC-Voltage7 | Inverter MPPT [7] Voltage (V DC) | SCADA (raw) | | | DC-Voltage8 | Inverter MPPT [8] Voltage (V DC) | SCADA (raw) | | | DC-Voltage9 | Inverter MPPT [9] Voltage (V DC) | SCADA (raw) | | | DC-Voltage10 | Inverter MPPT [10] Voltage (V DC) | SCADA (raw) | | | DC-Voltage11 | Inverter MPPT [11] Voltage (V DC) | SCADA (raw) | | | DC-Voltage12 | Inverter MPPT [12] Voltage (V DC) | SCADA (raw) | | | DC-Voltage13 | Inverter MPPT [13] Voltage (V DC) | SCADA (raw) | | | DC-Voltage14 | Inverter MPPT [14] Voltage (V DC) | SCADA (raw) | | | DC-Voltage15 | Inverter MPPT [15] Voltage (V DC) | SCADA (raw) | | | DC-Voltage16 | Inverter MPPT [16] Voltage (V DC) | SCADA (raw) | |